Data centers are buildings where large amounts of digital data are stored and processed. Security and reliability of these data are among the top priorities of any facility. Therefore, maintaining the required environment becomes a top priority to minimize disruptions to computer systems functionality.

Since data center equipment is highly energy-intensive, it generates significant amounts of heat during operation that must be effectively controlled and dissipated.
For ensuring reliable operation of equipment, environmental conditions in data centers are typically regulated by air conditioning and cooling systems. However, these systems can account for a substantial share of total energy consumption (often 30–50%) if not properly managed.
Optimizing the operation of air conditioning and cooling systems requires continuous monitoring and control of ambient temperature (T) and relative humidity (%RH). Therefore, the installation of RH/T transmitters is essential for providing real-time data on environmental conditions. This enables precise control of these parameters and improves overall cooling system efficiency and energy performance.
Acceptable ranges for these parameters may vary depending on facility design and local applicable regulatory requirements, but it is usually recommended to keep environmental conditions between 40 %RH and 60 %RH, 21 °C and 23 °C.
Deviations from the limits can negatively affect equipment lifetime, leading to data corruption and costly downtime. Elevated temperatures may cause systems to slow down, malfunction, or suffer permanent damage. Similarly, excessive humidity can result in corrosion, while insufficient humidity may lead to electrostatic discharge, particularly in colder climates where the air contains less moisture, potentially damaging sensitive electronic components.
The reliable operation of data centers also depends in part on backup power systems, including battery installations that are continuously maintained in a charged or ready state. During operation, batteries can emit hazardous gases, especially under conditions such as overcharging, discharging, aging or malfunction. The accumulation of such gases may lead to the formation of a toxic and potentially explosive atmosphere or be an early indicator of thermal runaway .
Gases that typically need to be detected include:

● Hydrogen (H2) is a colorless, odorless, and highly flammable gas and can form an explosive atmosphere with air. The lower explosive limit (LEL) of hydrogen is approximately 4% by volume (100% LEL corresponds to 4 vol.% H₂). In safety systems, alarm thresholds are typically set at 10–25% of the LEL to provide early warning and allow preventive ventilation or shutdown measures.
● Electrolyte vapours (including DEC and DEMC) are also colorless and consist of several different gases.
Such vapours are early indicators of thermal runaway and can be detected by a VOC gas detector.
● Carbon monoxide (CO) is another hazardous gas that is colorless, odorless, and highly toxic even at relatively low concentrations. Exposure limits vary depending on international standards, but typically CO time-weighted average (TWA) is 25–35 ppm and short-term exposure limits (STEL) are 100–200 ppm.
Gas detectors are essential for triggering alarms before dangerous gas concentrations are reached while RH/T transmitters help to monitor important environmental conditions.
When combined with traditional fire alarm and SCADA systems, gas detectors and RH/T transmitters significantly improve overall safety and optimize the operation of air conditioning and cooling systems.

Humidity and temperature transmitter E2218 is a member of new PluraSens ® family of multifunctional measurement instruments. The transmitter is…

Humidity and temperature transmitter E2228 is a member of new PluraSens ® family of multifunctional measurement instruments. The transmitter is…

E2244 features 4 analog outputs 2x4-20 mA and 2x0-10 V for connection to various secondary instruments and controllers, BMS systems.

EK30 one-sided light module is intended to warn people in areas, where hazardous concentrations of gas can accumulate. The module has visual and…

EK32 double-sided light module is intended to warn people in areas, where hazardous concentrations of gas can accumulate. The module has visual and…

EK60 one-sided single sided light module is intended to warn people in areas, where hazardous concentrations of gas can accumulate. The module has…

A sonda de temperatura e ponto de orvalho DMP5 Vaisala DRYCAP® foi desenvolvida para medição de umidade em linha em aplicações de secagem industrial…

Lauri Reuter é um especialista no futuro da alimentação e a pessoa certa para perguntar se você já se perguntou o que comeremos no futuro e como toda…

As empresas industriais continuam a tomar medidas para minimizar as suas emissões de carbono. Muitos estão a reduzir a utilização de combustíveis…

No processo de caustificação, os produtos químicos passivos são convertidos em produtos químicos ativos para cozinhar para produzir licor branco…
Um especialista responde com a solução, o instrumento e o serviço adequados.
Produtos para cotar
Ainda não há produtos. É possível escrever mesmo assim: um especialista responde.