Humidity and Temperature Transmitter Series HMW90
±1.7%RH wall transmitters with a certificate for demanding HVAC
Technical note
Cooling tower control systems depend on accurate and reliable humidity measurement to increase energy efficiency and reduce maintenance costs.

In HVAC applications, evaporative cooling towers remove heat from the condenser water – water used to cool the refrigerant – in chillers of HVAC systems. During this refrigerant-to-water heat exchange, the refrigerant temperature decreases and the condenser water temperature increases. The heated condenser water is then circulated to the cooling tower, where it is sprayed or splashed onto complex ventilated surfaces, maximizing evaporation that removes heat from the water. The cooled condenser water is then returned to the chiller to continue the cycle.

Excessive operation leads to several areas of avoidable operational and capital costs: wasting energy to run the fans more than needed, premature equipment repair, acceleration
of mineral build up in the tower fill, and inefficient water use from adding more water to the sump to replace the evaporated water. In one case that Wilcox cites, investigations concluded that inaccurate readings from an on-site RH device contributed to a cooling tower at a landmark hotel being so excessively run that the tower fill became nearly rock solid with calcium carbonate deposits. Uneven air flow rising through the plugged fill caused the tower system to be on the verge of shaking apart, damaging the fans and fan shrouds. Operators used fire hoses to keep the chiller plant operating at the height of the summer tourist season. Avoidable capital costs added up to hundreds of thousands of dollars to replace the tower fill.
Vaisala Recommended “Humidity measurements need to be accurate and maintainable. We specify Vaisala humidity sensors that we can count on not to migrate into error. We avoid recommending instruments that can go out of calibration in six months, misinforming the control systems and building operators,” says Wilcox. “We see projects that can spend
$200,000 a year on cooling tower related operating costs operated by a $50 sensor that goes unreliable in months. Life is too short to deal with error-prone devices.”
The Vaisala Humicap® HMT330 Series Humidity and Temperature Transmitter delivers high accuracy and excellent long-term stability, even in harsh outdoor conditions. RH accuracy is within 1% up to 90% RH and within 1.7% up to 100% RH. Temperature accuracy is within 0.2°C (0.36°F). The transmitters calculate wet-bulb temperature and can be field calibrated to meet the operator’s quality management protocol.
Wilcox recently reviewed cooling tower performance at an undisclosed data center in Utah. One of the recommended upgrades was to replace their RH device with the more accurate
Vaisala instrument. Now using accurate RH in the wet-bulb temperature measurement, the facility could reduce energy costs by using more free cooling. Free cooling can be used when the outdoor wet-bulb temperature plus the approach is lower than the requirement for primary chilled water. Under these conditions, the condenser water cools the primary
chilled water, bypassing the chiller entirely. Free cooling reduces mechanical cooling costs, is more energy efficient, and is recognized as a green energy effort. With accurate wet-bulb temperature measurements, the data center was able to convert to free cooling for more than half the year and still meet its cooling requirements.
The value of accurate RH measurements is increasing as more cooling tower builders, operators, and HVAC professionals learn – still too often the hard way – that more reliable
sensors using advanced technology can pay for themselves many times over.

±1.7%RH wall transmitters with a certificate for demanding HVAC

Upper air soundings provide the crucial data necessary for a complete atmospheric weather profile that leads to accurate forecasting. However…

Vaisala Automatic Weather Station AWS310 is a complete communication and weather observation solution that can be used as a standalone unit, or as…

Our next-generation, cyber secure and modular Maritime Automatic Weather Station AWS830 is engineered for harsh marine environments and compliant…

The Vaisala Automatic Weather Station AWS810 enables modern, high-quality surface weather observation networks anywhere in the world.

Vaisala Maritime Automatic Weather Station AWS830 delivers accurate, always‑on weather, environmental, oceanographic, and motion data for demanding…

Vaisala DRYCAP® Dew Point and Temperature Probe DMP5 is designed for in-line humidity measurement in industrial drying applications with high…

Dr. Lauri Reuter is an expert in the future of food, and the person to ask if you’ve ever wondered what we are going to eat in the future, and how…

Industrial companies are continuing to take action to minimize their carbon emissions. Many are reducing their use of fossil fuels and switching to…

In the causticizing process, passive chemicals are converted into active cooking chemicals to make white liquor. This is used in the digester as a…
A specialist replies with the solution, the instrument and the service that fit.
Products to quote
No products yet. An enquiry can be sent anyway: a specialist answers.