We have analyzed the as-found results from service calibrations performed in our Helsinki, Boston, Tokyo, and Beijing service centers. Although we have no information on how the probes have been used we assume that most of them are used to monitor conditions in cleanrooms or datacenters, which are typically not very demanding applications for these products. We analyzed about 5,000 calibrations for 2,000 individual HMP110 probes, with some probes being calibrated multiple times. We assumed that no other adjustments had been performed during the lifetime of the probes. The as-found RH errors at 0%RH and 75%RH, as well as the ambient temperature measurement, were plotted against the time since the previous calibration:


After two years the main statistics for the as-found errors are as follows:
|
0%RH |
75%RH |
Temperature °C |
|
|
Average |
-0.01%RH |
-0.32%RH |
0.00°C |
|
Standard deviation |
0.18%RH |
0.88%RH |
0.10°C |
(Extreme outliers have been removed, leaving 170samples.
Without going too deep into the statistical analysis, our main conclusions are that:
most of the probes have remained within their as-new specification (±1.5%RH/0.1 °C) even after two years of use
the drift estimates for uncertainty calculations of ±0.5%RH/year and ±0.02 °C/year seem fair

For high precision measurements in demanding HVAC applications

For use up to zone 0 and 20

±1.7%RH wall transmitters with a certificate for demanding HVAC

Vaisala Weather Transmitter WXT530 series is a unique collection of cost-effective sensors that accurately and reliably measure weather conditions…

Vaisala Weather Transmitter WXT530 series is a unique collection of cost-effective sensors that accurately and reliably measure weather conditions…

Upper air soundings provide the crucial data necessary for a complete atmospheric weather profile that leads to accurate forecasting. However…

Vaisala DRYCAP® Dew Point and Temperature Probe DMP5 is designed for in-line humidity measurement in industrial drying applications with high…

Dr. Lauri Reuter is an expert in the future of food, and the person to ask if you’ve ever wondered what we are going to eat in the future, and how…

Industrial companies are continuing to take action to minimize their carbon emissions. Many are reducing their use of fossil fuels and switching to…

In the causticizing process, passive chemicals are converted into active cooking chemicals to make white liquor. This is used in the digester as a…
A specialist replies with the solution, the instrument and the service that fit.
Products to quote
No products yet. An enquiry can be sent anyway: a specialist answers.