Technical note

Lithium-ion batteries become central element of modern energy infrastructure, particularly in such applications as:
• Battery energy storage systems (BESS)
• Data centers and UPS rooms
• EV charging stations
• Battery manufacturing facilities
For this reason, ensuring their safe operation is more critical than ever.
Among the most serious risks are battery thermal runaway and off-gassing. These are failure mechanisms that can escalate rapidly and lead to fires and explosions.
Understanding how these events occur, what causes them, and how they can be detected at the earliest possible stage is essential for designing effective safety strategies and protecting people and facilities.
Thermal runaway is a self-accelerating failure process in which an increase in battery temperature triggers internal reactions that generate even more heat. Once initiated, thermal runaway can escalate rapidly, leading to cell venting, fire, or explosion.
In lithium-ion batteries, thermal runaway typically begins at the cell level, but can propagate to modules, racks, and entire containers if not detected and mitigated early.
Thermal runaway does not occur spontaneously, it is initiated by specific abuse or fault conditions.
The most common causes include:
• Electrical abuse (overcharging, over-discharging, internal short circuits caused by manufacturing defects)
• Thermal abuse (inadequate cooling and ventilation, high ambient temperatures)
• Mechanical abuse (transportation or operation damage, improper installation)
• Aging and degradation
• Manufacturing defects
Off-gassing refers to the release of gases from a battery cell due to overheating, decomposition of internal materials, or venting during failure. Off-gassing can occur well before ignition, making it one of the earliest indicators of a thermal runaway event.
In addition, such gases can accumulate rapidly, creating a serious hazard.
During lithium-ion battery off-gassing a complex mixture of flammable, toxic and asphyxiant gases is emitted, including:
Hydrogen (H₂) - colorless, odorless, highly flammable.
Carbon Monoxide (CO) - colorless, odorless, highly toxic for humans (even at low concentrations).
Volatile Organic Compounds (VOCs) - electrolyte vapours which are colorless and can be flammable.
Classic fire detection systems typically rely on smoke, heat and flame detectors.
Due to battery failure detection specifics, such systems may not trigger in the earliest stages of battery failure, and here is why:
No smoke in early stages.
Off-gassing occurs before combustion. At this stage, there may be no smoke, no visible flame, no significant temperature rise in the room. Smoke detectors therefore remain inactive while a dangerous condition is already developing.
Delayed heat release.
Thermal runaway begins inside of a cell. External temperature rise may be minimal initially. Heat detectors respond too late to prevent escalation. By the time heat alarms trigger, multiple cells are already in thermal runaway process.
Flame detection is reactive, not preventive.
Flame detectors only activate after ignition, offering no early warning.
H2, VOC and CO gas detectors play a key role in ensuring safety, as they enable detection of the earliest signs of battery cell failure.
Such detectors need to have RS485 Modbus RTU and relays to communicate with various fire control panels or SCADA systems, allowing timely reaction to potential emergency situations.
When combined with traditional fire alarm systems, gas detectors significantly improve overall safety, reducing the risk of an incident.

Vaisala DRYCAP® Dew Point and Temperature Probe DMP5 is designed for in-line humidity measurement in industrial drying applications with high…

Dr. Lauri Reuter is an expert in the future of food, and the person to ask if you’ve ever wondered what we are going to eat in the future, and how…

Industrial companies are continuing to take action to minimize their carbon emissions. Many are reducing their use of fossil fuels and switching to…

In the causticizing process, passive chemicals are converted into active cooking chemicals to make white liquor. This is used in the digester as a…
A specialist replies with the solution, the instrument and the service that fit.
Products to quote
No products yet. An enquiry can be sent anyway: a specialist answers.