A unit of AKRIBIS One

TEV_LU-Series

Frost guard Temperature Transmitter TEV LU

TEV LU temperature transmitter is designed for air-handling unit radiator monitoring. The transmitter is suitable also for domestic water applications due the short time constant. Pt1000 sensor element resistance information is converted to a 0...10 V signal. The ML-SER commissioning tool can be used to make one point field calibration and to change the temperature output to controller output.

Request a quoteDownload the datasheet

Frost guard Temperature Transmitter TEV LU

Technical data

Power supply24 Vac/dc, < 1 VA
Temperature measurement range0...50 °C, 0...100 °C, -50...50 °C, -50...150 °C
Temperature measurement accuracy±0.5 °C
SensorPt1000 EN 60751/B
Pressure ratingPN16
Voltage output0...10 Vdc, 2 mA (temperature or controller)
IP protection classIP54
IP protection class notecable downwards
Cable glandM16
Mountingprobe: R ¼”, housing: with screws
Materialsacid proof steel, brass, PC plastic

Configure the instrument

Choose the model, probes and accessories. Incompatible combinations are blocked as you go; the remaining rules are checked when the instrument is added to the quote.

Documents

  • ML-SER

    Configuration tool ML-SER

    ML-SER commissioning tool is designed for easy commission and configuration of Produal first-generation transmitters. The ML-SER shows…