A unit of AKRIBIS One

Application note

Dew Point in Data Centers

A data center needs to keep humidity within a narrow range: not so dry that it raises the risk of static electricity, nor so humid that it favors condensation or hardware corrosion. For the general context of this magnitude, see the humidity instrumentation landing.

Climate control and ventilation account for a significant share of a data center's energy consumption — cooling alone concentrates much of that demand. That's why humidity measurement quality isn't a minor detail: a measurement error translates directly into wasted HVAC energy.

This note covers

  • The temperature and humidity ranges ASHRAE recommends for IT equipment
  • Why dew point is a more stable control parameter than relative humidity
  • How sensor accuracy directly affects HVAC energy consumption

The Ranges ASHRAE Recommends

ASHRAE guidelines for data center environmental conditions recommend an inlet air temperature range of 18 to 27°C and relative humidity of 25% to 80% (equivalent to a dew point between 5 and 15°C). Straying from that range in either direction has consequences: air that's too dry raises the risk of static electricity discharge onto equipment; air that's too humid favors condensation and, over time, corrosion of electronic components.

Staying within that range with margin is the foundation of any climate control strategy — but sustaining it energy-efficiently depends on which variable is used to control the system.

Why Dew Point Instead of Relative Humidity

Relative humidity depends on the temperature at the point where it's measured: the same air mass can give different RH readings at two points in the data center that are at different temperatures, even though they contain the same amount of water vapor. This complicates coordinating control between zones with different inlet temperatures.

Dew point, on the other hand, doesn't depend on the sensor's temperature — it only varies with pressure. That's why data centers seeking a robust climate control strategy prefer to use dew point as the control parameter: it allows humidification and dehumidification to be coordinated consistently across the entire facility, regardless of what temperature point the reading is taken at.

Sensor Accuracy Has a Direct Energy Impact

A data center's temperature and humidity control strategy is only as good as the measurement equipment behind it — even small measurement errors can increase the energy bill significantly. A poorly calibrated sensor, or one that drifts over time, can cause the system to over-humidify or over-dehumidify, spending energy correcting a condition that was actually already within range.

With accurate, stable humidity and dew point measurement, it becomes possible to make the most of efficiency strategies like adiabatic cooling or outdoor air economizers — maximizing hours of free cooling without straying outside the humidity limits that protect the equipment.

This technical content is based on Vaisala's documentation on environmental monitoring and energy efficiency in data centers. AKRIBIS is an authorized Vaisala partner for distribution and technical support in the region — explore the full Vaisala instrumentation line. For the specific probe for your server room, consult a specialist.

Instruments to Measure Humidity

See the full Humidity instrumentation landing →
A server aisle in a data center with continuous environmental monitoring.
A server aisle in a data center with continuous environmental monitoring.

Instruments for measuring humidity

Application note

See all

A question about your measurement

A specialist replies with the solution, the instrument and the service that fit.

Talk to a specialist

Write on WhatsApp