A data center needs to keep humidity within a narrow range: not so dry that it raises the risk of static electricity, nor so humid that it favors condensation or hardware corrosion. For the general context of this magnitude, see the humidity instrumentation landing.
Climate control and ventilation account for a significant share of a data center's energy consumption — cooling alone concentrates much of that demand. That's why humidity measurement quality isn't a minor detail: a measurement error translates directly into wasted HVAC energy.
ASHRAE guidelines for data center environmental conditions recommend an inlet air temperature range of 18 to 27°C and relative humidity of 25% to 80% (equivalent to a dew point between 5 and 15°C). Straying from that range in either direction has consequences: air that's too dry raises the risk of static electricity discharge onto equipment; air that's too humid favors condensation and, over time, corrosion of electronic components.
Staying within that range with margin is the foundation of any climate control strategy — but sustaining it energy-efficiently depends on which variable is used to control the system.
Relative humidity depends on the temperature at the point where it's measured: the same air mass can give different RH readings at two points in the data center that are at different temperatures, even though they contain the same amount of water vapor. This complicates coordinating control between zones with different inlet temperatures.
Dew point, on the other hand, doesn't depend on the sensor's temperature — it only varies with pressure. That's why data centers seeking a robust climate control strategy prefer to use dew point as the control parameter: it allows humidification and dehumidification to be coordinated consistently across the entire facility, regardless of what temperature point the reading is taken at.
A data center's temperature and humidity control strategy is only as good as the measurement equipment behind it — even small measurement errors can increase the energy bill significantly. A poorly calibrated sensor, or one that drifts over time, can cause the system to over-humidify or over-dehumidify, spending energy correcting a condition that was actually already within range.
With accurate, stable humidity and dew point measurement, it becomes possible to make the most of efficiency strategies like adiabatic cooling or outdoor air economizers — maximizing hours of free cooling without straying outside the humidity limits that protect the equipment.
This technical content is based on Vaisala's documentation on environmental monitoring and energy efficiency in data centers. AKRIBIS is an authorized Vaisala partner for distribution and technical support in the region — explore the full Vaisala instrumentation line. For the specific probe for your server room, consult a specialist.


for monitoring temperature, humidity, with optional analog input

How infrared sensors work, temperature/pressure/humidity compensation, and transmitter placement.

Why CO2 is critical in cell culture, the risk of condensation when measuring in high humidity and temperature, and why sterilization without removing…

Why O2 is lowered and CO2 raised in controlled-atmosphere rooms, and which instruments withstand the cold and high humidity of this environment.

What equilibrium sampling is, why sensor heating can skew field measurements, and what range is needed for deep soil profiles.
A specialist replies with the solution, the instrument and the service that fit.
Instruments to quote
No instruments yet. An enquiry can be sent anyway: a specialist answers.