CAB100 Industrial Cabinet for continuous monitoring systems
for cleanrooms and industrial settings
Technical note
Back for more on Mean Kinetic Temperature with a customer question:
Hi Paul,
I have reviewed Vaisala’s application note on mean kinetic temperature. But, I am still wondering what particular guidance states that mean kinetic temperature should only be used for room temperature environments and not for refrigerators or freezers? That is Rule #5 on your 6 rules for MKT.
But I’m still unclear to me exactly why not to use it in colder temperatures. Your assistance is greatly appreciated.
Thank you!
K
Dear K,
Thank you for checking out our training materials! We are happy to provide these to our customers and contacts in the industry at large. Here are the links to the webinar and the application note.
First off, you are not alone in your question, so below I have listed several questions we received in our last webinar on mean kinetic temperature. You will see that your question about cold chambers was asked then as well. And it is a very common question.
Second, to review our application note and the rules you mention, I will list all of them again here.
6 Mean Kinetic Temperature Usage Recommendations:
Finally, the answer to your question: Why Not Use MKT in Cold Chambers?
Because the best guidance we can use, and probably the only one to use in regulated environments, is the source of the idea that we can use mean kinetic temperature to evaluate temperature excursions: John Taylor.
Here is the name of the paper: The Pharmaceutical Journal (Vol 267), July 2001, J. Taylor. “Recommendations on the Control and Monitoring of Storage and Transportation Temperatures of Medicinal Products.”
I draw your attention to the lower left-hand corner of page 131 in the paper:
Strict conditions should be applied to the use of mean kinetic temperature. It is applicable only to storage of products under controlled room temperature conditions (I.E., those labeled “do not store above 25°C”). Mean kinetic temperature can be applied to the shipping of these products and it may provide a degree of assurance during prolonged transit periods. Mean kinetic temperature is not appropriate for products requiring controlled low temperature storage and shipping.
This paper basically brought the mean kinetic temperature calculation into its current use and describes how and why to use it. Simply put, the guy who first thought that MKT might be good for evaluating excursions also explicitly stated where not to use it, saying: “[MKT] is not appropriate for products requiring controlled low temperature storage and shipping.” It was a great innovation in its time, but we recommend sticking to the original guidance that accompanied the use of mean kinetic temperature.
That’s why we made recommendation 5 in our application note. We can also find that rates of change in chemical reactions and degradation pathways further support this position. Our caution against using the value for cold chamber applications is directly from the seminal paper on the topic, but also from the likelihood that you might have an uphill battle convincing an auditor that mean kinetic temperature for refrigerated chambers is a better solution for evaluating excursions than the other tools we at our disposal. Please contact me further if you have any questions!
Paul Daniel

for cleanrooms and industrial settings

for refrigerant dryers

for OEM applications

for quick inspections and spot-checking

For high precision measurements in demanding HVAC applications

Vaisala Humidity Calibrator HMK15 makes calibration and spot checking of humidity probes and transmitters easy and reliable, although for critical…

What relative humidity, dew point, absolute humidity and mixing ratio are, how temperature and pressure distort the reading, and why dew point is…

How humidity behaves in real conditions, the three most common measurement problems, and two practical scenarios —heated air and compressed air—…
When to measure relative humidity vs. dew point, what high and low humidity demand, how temperature and pressure factor in, and when a warmed probe…

Cooling accounts for up to 40% of a data center's energy demand. This Vaisala guide explains how measurement accuracy cuts costs and risks, with a…
A specialist replies with the solution, the instrument and the service that fit.
Instruments to quote
No instruments yet. An enquiry can be sent anyway: a specialist answers.